Does the WIN-911 Standard/Interactive/Advanced license support local announcer or PA systems?


No, the local announcer feature from V7 is not available on the new license.


However, it is possible to have WIN-911 dial into a PA system and announce the alarms using TAPI or VoIP. For this feature to work you must be able to dial into the PA system and the PA System will need to be added to WIN-911 as a contact. Next configure the PA system contact as a "Non-Interactive" connection. 


Interactive

This mode of alarm notification is a two way dialog between WIN-911 and the user. It requires the recipient to enter an authorization code and can be configured to allow remote acknowledgements by use of an ack code. The user can optionally be given permission to make inbound calls to request alarm conditions and reports. 

 

Non-Interactive

This mode of alarm notification is a one way transmission of alarm messages. It only conducts outbound calls, reports the alarm conditions, and disconnects the call on completion. It is intended for public address announcements and leaving messages on voicemail. It does not accept user input or answer inbound calls. 








Technical support

To start a support case, you will need your Maintenance Support number or your CD Tracking number. CLICK HERE to open a new support case.